Omron PLC CPM2A and NT11 solution
Question: I have a PLC and a CPM2A pt.I NT11′ve read the instructions NT11 where digital data is input to the NT11, it is automatically transmitted to the PT status notify area allocated to the memory controller as follows.

I defined the area to notify DM800, and he says he is a figure setting strobe flag is activated when an update of the data occurs (when the Enter key is pressed). Now, my problem is that I understand where he is the one indicator flash rate environment, and how I can check in the Ladder Logic plc? The guide is a simple pattern scale of the problem (I’m on this page), but in this diagram, the flag `s address is 11211, but I did not find this address.
So my answer is that how can I discover in Ladder Logic plc after an entry figure I press the ENTER key on the NT11?
Help
PLC Program
Create the following PLC ladder program
Program operation
1.When the numeral setting flag(bit 11211) comes ON(1)
,the contests of CIO/IR 0111(the word where the content upgrade memory table entry is located)
are transferred to DM0105.
The number of the numeral memory table entry that contains the upgraded data is stored in DM 0105
(in this case it is 003 or 004).
If the numeral memory table entry is allocated to a PLC word,the value in put to it can be read easily by referring to the allocated word.
In this case ,the contents of numeral memory table entry No.3 are stored in DM 0005 and the content of numeral memory table entry No.4 are stored in DM006
Answer: The control NT11 / Hold field would be better placed in a different area of memory.
The area in the DM series CPM is not only “area.
The Numeral setting strobe flag in the word Bit11 m 2.
Example: if the zone is to prevent H10, the rate setting strobe flag
would H12.11 bit